AGRS - 30/2

PHOTO CIRCUITRY QUISTIONNAIRE

 

AGDS “Goluboe plamya” 30/2 is designed for:
- purifying natural gas and associated petroleum gas from mechanical impurities and condensate moisture;
- reducing high gas pressure to specified low pressure and maintaining it of a specified accuracy;
- gas and heat carrier heating;
- gas flow rate measurement;
- automatic control and regulation of AGDS technological process.
AGDS consists of:
- switch unit;
- process unit;
- instrumentation unit;
- gas heating unit;
- gas odorization unit – 2 pics.

AGDS is operated outdoor in macroclimatic regions of temperate climate design U, location category 1 according to GOST 15150-69. Estimated snow load is 240 kgs/m2 according requirements VI of territorial district, and wind load is 38 kgs/m2 according to requirements III of territorial district  by SNiP 2.01.07-85. Explosion hazard zone class of process unit is in accordance with the Rules for electric devices operation – В-1а. Fire hazard category of process unit is in accordance with NPB-105-03 ? А. Fire resistance degree of unit by SNiP 21-01-97 is II.

The main technical characteristics of AGDS are shown in the table.

Parameters Value
Minimum gas pressure, МPа 1,5
Maximum pressure, МPа 5,4
Test gas pressure, МPа 8,1
Maximum throughput capacity, nm3/h 30000
Minimum throughput capacity, nm3/h 1100
Designed efficiency at the output №1, nm3/h from 800 to 22000
Designed efficiency at the output №2, nm3/h from 300 to 8000
Gas temperature at the input, 0С minus 1?plus 10
Environment temperature, 0С minus 43?plus 39
Overhaul life, not less than, h 175200
Main power voltage, V 220
Emergency power voltage, V 220
Allowable seismic activity of station installation region,
points on the Richter scale according to SNiP II-7-81
7
Overall dimensions (length?width?height), m
? switch unit;
? process unit;
? instrumentation unit;
? gas heating unit;
? gas odorization unit – 2 pics.

5,0х3,0х3,07
7,5?5,0?3,04
6,0?3,0?2,9
7,0?3,0?3,17
2,75х1,8х1,0
Mass, not more than, kg
? switch unit;
? process unit;
? instrumentation unit;
? gas heating unit;
? gas odorization unit – 2 pics.

10 000
20 000
7 000
12 000
1 000
Service life, years, not less than 30

 

Overhaul life, not less than, h

Запрос стоимости оборудования