The automatic gas pressure reduction and metering station in block version is used for reducing and maintaining natural or casing-head gas from high to the required low pressure, and also for gas consumption metering and odorization before vendor supply.

Designation, parameters and characteristics

Value

1

2

Minimum inlet gas pressure, MPa

2,6

Maximum inlet gas pressure, МPа

5,5

Testing gas pressure, МPа

8,25

Maximum capacity,

nm3 /h

for boiler room

2600

Gas-turbine electrostations

6600

Minimum capacity,

nm3 /h

for boiler room

300

Gas-turbine electrostations

500

Gas pressure, МPа

for boiler room

0,6

Gas-turbine electrostations

1,2

Inlet gas temperature, 0С

maximum

below 28

minimum

under 55

Outlet gas temperature AGPRMS, 0С

below 30

Accuracy of outlet gas pressure maintenance AGPRMS, %

±5

specified service life before capital repairmen t,

not less, h

175200

Voltage of the main supply, volt

380/220

Voltage of the emergency supply, volt

220

Quantity of outlets for vendors

two

Allowed seismicity of the area of station placement,

earthquake magnitude on the Richter scale

6

Dimensions (length?width?height), m:

- technological block

- gas heating block

 

11,6?3,36?3,0

12,0?3,5?3,15

Mass, not more, kg:

- technological block

- gas heating block

 

18000

22000

Life time, yeas, not less

30